The powerhouse

Vario II

The Vario II single-room ventilation unit is powerful, easy to install and (apart from filter changes) completely maintenance-free. Design your single-room ventilation unit from your choice of surface-mount or flush-mount box and fan insert to meet your needs.

  • Protection against moisture damage
  • Prevention of mould formation
  • Several different control options
  • High airflow rate due to steep pressure-volume flow rate characteristic
  • Fire protection possible with only 230 mm height offset

Installation options for VARIO II

When it comes to installing our single-room ventilation units, you can choose a flush-mount or surface-mount solution. For detailed information on installation or fire protection, we are happy to give you personal advice. Or you can download our brochure.

Single-room ventilation units brochure (PDF)

Request information

Installation dimensions

Types U, UB, UBK

Installation dimensions

Types U-H, UB-H, UBK-H

*Dimensions for box without fire protection casing

Installation dimensions

Types A, AK

Installation positions for Flush-mount / Surface-mount box

Exhaust socket to rear

A flush- or surface-mount installation with the exhaust socket to the rear allows you to rotate the box by 360°. The socket can be placed at the top left, top right, bottom left or bottom right, as needed.

Types: A, AK, U-H, UB-H, UBK-H

Single-room ventilation units brochure (PDF)

Installation positions for flush-mount box

Exhaust socket to the side

Flush-mount installation with the exhaust socket to the side also allows you to rotate the box. The socket can be placed to the left, top or right, as needed.

Types: U, UB, UBK

Single-room ventilation units brochure (PDF)

Installation positions for flush-mount box

Exhaust socket to the side recessed in the ceiling

Our powerful and reliable single-room ventilation unit VARIO II can also be recessed in the ceiling.

Types: U, UB, UBK

Single-room ventilation units brochure (PDF)

COMBINABLE WITH ALL VARIO II BOXES

VARIO II functions

The single-room ventilation unit VARIO II offers a wide range of fan inserts with different control options. The motors let you choose between one, two or three ventilation levels. You can combine the fan inserts with all boxes available with the single-room ventilation unit VARIO II.

Single-room ventilation units brochure (PDF)

With filter holder, air filter and cover

Single-stage fan inserts

The fan starts as soon as the unit is switched on and stops as soon as the unit is switched off.

Name of part:
Part no: 2200 V-II 30
Part no.: 2210 V-II 60
Part no.: 2220 V-II 100

Ventilation to DIN 18017-3, also V-II 30-N for use in toilet rooms

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer for easy setting. When the unit is switched on, the fan starts after a switch-on delay of 1 min (factory setting). When the unit is switched off, the fan stops working after a 15 min run-on time (factory setting).

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2205 V-II 30-N
Part no.: 2215 V-II 60-N
Part no.: 2225 V-II 100-N

Integrated interval and run-on control. Potentiometer for easy setting.

The fan starts as soon as the unit is switched on.

When the unit is switched off, the fan stops working after a 15 min run-on time (factory setting). Interval mode starts after the last time the fan was switched off. The fan is out of use for the default interval time of approx. 1 h (factory setting). The fan then runs on for 15 min (factory setting).

Possible settings:

  • Infinitely-variable run-on time from 3 to 20 min
  • Infinitely-variable interval mode from 1 h to 12 h

Name of part:
Part no.: 2206 V-II 30-I
Part no.: 2216 V-II 60-I
Part no.: 2226 V-II 100-I
 

Ventilation to DIN 18017-3

Integrated run-on control for infinitely-variable adjustment of the run-on time. Potentiometer for easy setting. The motion detector registers people within the detection range and triggers a switching signal. The fan starts immediately. When the person leaves the detection range, the fan stops working after a 15 min run-on time (factory setting). If the motion detector registers a person before the run-on time has elapsed, the run-on time restarts when the person leaves the detection range.

Possible settings for motion detector: Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2203 V-II 30-BM-N
Part no.: 2213 V-II 60-BM-N
Part no.: 2223 V-II 100-BM-N
 

Ventilation to DIN 18017-3

Integrated run-on control for infinitely-variable adjustment of the run-on time. Potentiometer for easy setting. The motion detector registers people within the detection range and triggers a switching signal. The fan starts immediately. When the person leaves the detection range, the fan stops working after a 15 min run-on time (factory setting). If the motion detector registers a person before the run-on time has elapsed, the run-on time restarts when the person leaves the detection range. Interval mode starts after the last time the fan was switched off. The fan is out of use for the default interval time of approx. 1 h (factory setting). The fan then runs on for 15 min (factory setting).

Possible settings for motion detector:

  • Infinitely-variable run-on time from 3 to 20 min
  • Infinitely-variable interval mode from 1 h to 12 h

Name of part:
Part no.: 2204 V-II 30-BM-I
Part no.: 2214 V-II 60-BM-I
Part no.: 2224 V-II 100-BM-I
 

The humidity control has a fixed switching point of 75 % RH (relative humidity) or responds to a rapid rise in humidity. When the unit is switched on, the fan starts after the measured values have been recorded for approx. 50 s (60 or 100 m3/h). When the unit is switched off, the fan runs on for 15 min. The fan switches off if no increased humidity value is measured during this period. The humidity sensor has a measured control range from 20 % to 95 % RH and constantly monitors the room air humidity. The humidity sensor starts the fan in the following situations:

  • Rapid rise in humidity regardless of the current room air humidity
  • The switching point of 75 % RH is exceeded

The integrated tropics function adapts the humidity sensor to the atmosphere in the room which changes according to the time of year. The tropics function also incorporates a running time limiter which switches the fan off after 12 h of uninterrupted service. Example of a rapid rise in humidity: The room humidity is 45 % RH. While the shower is in use, the fan starts due to the rapid rise in humidity, even if the 75 % RH switching point has not yet been reached.

  • Fan running at 60 or 100 m3/h
  • Run-on time of 15 min
  • Measured control range from 20 % to 95 % RH
  • Fixed switching point of 75 % RH
  • Responds to a rapid rise in humidity regardless of the current room air humidity (RH)
  • Running time limiter

Name of part:
Part no.: 2217 V-II 60-F
Part no.: 2227 V-II 100-F

With filter holder, air filter and cover

Two-stage fan inserts

The fan runs continuously either in base load operation (30 m3/h) or in nominal load operation (60 or 100 m3/h).

A switch is used to toggle between base load operation and nominal load operation.

  • Continuous base load operation at 30 m3/h
  • While the room is in use, nominal load operation at 60 or 100 m3/h

Name of part:
Part no.: 2230 V-II 30/60
Part no.: 2240 V-II 30/100

Ventilation to DIN 18017-3

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer for easy setting.

The fan runs continuously in base load operation (30 m3/h). When the unit is switched on, the fan runs in nominal load operation after a switch-on delay of approx. 1 min (60 or 100 m3/h) (factory setting). When the unit is switched off, the fan runs on for 15 min in nominal load operation (factory setting). The fan then switches to base load operation.

  • Continuous base load operation at 30 m3/h
  • Nominal load operation at 60 or 100 m3/h
  • Run-on time in nominal load operation at 60 or 100 m3/h

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2231 V-II 30/60-NZ
Part no.: 2241 V-II 30/100-NZ

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer for easy setting. When the unit is switched on, the fan runs in base load operation after a switch-on delay of approx. 1 min (30 m3/h) (factory setting). When the unit is switched off, the fan runs on for 15 min in nominal load operation (60 or 100 m3/h) (factory setting). The fan then switches off.

  • While the room is in use, base load operation at 30 m3/h
  • Run-on time in nominal load operation at 60 or 100 m3/h

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2232 V-II 30/60-K
Part no.: 2242 V-II 30/100-K

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer for easy setting. When the unit is switched on, the fan runs in base load operation after a switch-on delay of approx. 1 min (30 m3/h) (factory setting). When the unit is switched off, the fan runs on for 15 min in nominal load operation (60 or 100 m3/h) (factory setting). The fan then switches off. This control is also equipped with a remote control input (230 V AC, internal, switchable via potential-free contact) to allow base load operation to be switched on and off using a switch provided by the customer.

  • While the room is in use, base load operation at 30 m3/h
  • Run-on time in nominal load operation at 60 or 100 m3/h
  • Base load operation switched on and off via a switch provided by the customer

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2233 V-II 30/60-KF
Part no.: 2243 V-II 30/100-KF

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer for easy setting. When the unit is switched on, the fan runs in base load operation after a switch-on delay of approx. 1 min (30 m3/h) (factory setting). When the unit is switched off, the fan runs on for 15 min in nominal load operation (60 or 100 m3/h) (factory setting) The fan then switches off. This control is also equipped with a remote control input (230 V AC, supplied externally) to allow base load operation to be switched on and off using a switch provided by the customer.

  • While the room is in use, base load operation at 30 m3/h
  • Run-on time in nominal load operation at 60 or 100 m3/h
  • Base load operation switched on and off via a switch provided by the customer

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2233-1 V-II 30/60-KF-LX
Part no.: 2243-1 V-II 30/100-KF-LX

Integrated run-on control for infinitely-variable adjustment of the switch-on delay and run-on time. Potentiometer on the fan for easy setting. When the unit is switched on, the fan runs in base load operation after a switch-on delay of approx. 1 min (30 m3/h) (factory setting). When the unit is switched off, the fan runs on for 15 min in nominal load operation (60 or 100 m3/h) (factory setting. The fan then switches off. This control is also equipped with a central control input for a 12/24 V AC control cable provided by the customer which is used to switch base load operation on and off from a central location.

  • While the room is in use, base load operation at 30 m3/h
  • Run-on time in nominal load operation at 60 or 100 m3/h
  • Base load operation switched on and off via a switch provided by the customer

Possible settings:

  • Infinitely-variable switch-on delay from 3 s to 2.5 min
  • Infinitely-variable run-on time from 3 to 20 min

Name of part:
Part no.: 2234 V-II 30/60-KZ
Part no.: 2244 V-II 30/100-KZ

Ventilation to DIN 18017-3 in combination with option Part no. 2250-01 V-II O/F-DG

The humidity control has a fixed switching point of 75 % RH (relative humidity) or responds to a rapid rise in humidity. When the unit is switched on, the fan runs in base load operation (30 m3/h) after the measured values have been recorded for approx. 50 s. When the unit is switched off, the fan runs on for 15 min in nominal load operation (60 or 100 m3/h) (factory setting). The fan switches off if no increased humidity value is measured during this period. The humidity sensor has a measured control range from 20 % to 95 % RH and constantly monitors the room air humidity. The humidity sensor switches the fan to base load operation in the following situations:

  • Rapid rise in humidity regardless of the current room air humidity
  • The switching point of 75 % RH is exceeded

The integrated tropics function adapts the humidity sensor to the atmosphere in the room which changes according to the time of year. The tropics function also incorporates a running time limiter which switches the fan off after 12 h of uninterrupted service in base load operation.

Example of a rapid rise in humidity:
The room humidity is 45 % RH. While the shower is in use, the fan switches to base load operation due to the rapid rise in humidity, even if the 75 % RH switching point has not yet been reached.

  • While the room is in use, base load operation at 30 m3/h
  • Run-on time of 15 min in nominal load operation at 60 or 100 m3/h
  • Humidity mode in base load operation at 30 m3/h

Designation:
Part no.: 2235 V-II 30/60-F
Part no.: 2245 V-II 30/100-F

For single-room ventilation units with humidity control, the following options are also available: central control input (timer), continuous base load operation, motion detector, remote control input.
For more information on these options, see our brochure

With filter holder, air filter and cover

Three-stage fan inserts

The fan starts immediately when the desired air flow (30, 60 or 100 m3/h) is selected with the 3-way stepping switch. The fan stops immediately when the 3-way stepping switch is moved to the zero position.
 

Name of part:
Part no.: 2670

CONTACT

Your local contact person 

You’re looking for an experienced ventilation partner for your construction project? Or you have general questions about ventilation systems? Our ventilation experts are happy to help!

Contact us now

ATTENTION

Please note that we will be on company vacations from 18.12.2024 to 12.01.2025 inclusive.
Your inquiries and orders will not be processed during this period. We will be back for you from 13.01.2025.
 

Thank you for your understanding.