VARIO II

ClassicLine fan inserts with intake kit For use with one power level

without control

Description:

Art.-No.: 2200 V-II 30
Art.-No.: 2210 V-II 60
Art.-No.: 2220 V-II 100

The Unit starts immediately switch-on.
The Unit stops immediately switching-off. 



With follow-up control

Description:

Art.-No.: 2205 V-II 30-N
Art.-No.: 2215 V-II 60-N
Art.-No.: 2225 V-II 100-N

Integrated after-run control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. The fan starts after switching on with a switch-on delay of 1 min *. After switching off, the fan terminates its operation after 15 min.

* factory-made adjustment

Adjustment options:

• Input delay continuous from 3 s until 2,5 min
• Follow-up time continuous from 3 until 20 min


With interval control

Description:

Art.-No.: 2206 V-II 30-I
Art.-No.: 2216 V-II 60-I
Art.-No.: 2226 V-II 100-I

Integrated interval and follow-up control. Easy adjustment via potentiometer. The fan starts immediately after switching on. After switching off, the fan terminates its operation after 15 min. Intermittent operation starts after the last fan shutdown. The fan is out of operation for the preset interval time of approx. 1 h *. The fan then runs for 15 min *. 

*  factory-made adjustment

Adjustment options:

• Input delay continuous from 3 until 20 min
• Interval mode continuous from 1 h until 12 h

With motion detector and follow-up delay

Description:

Art.-No.: 2203 V-II 30-BM-N
Art.-No.: 2213 V-II 60-BM-N
Art.-No.: 2223 V-II 100-BM-N

Integrated follow-up control for infinitely variable setting of the after-running time. Easy adjustment via potentiometer. The motion detector registers persons in the detection area and triggers a switching signal. The fan starts immediately. If the person leaves the detection area, the fan terminates its operation after 15 min * after-running time. If the motion detector detects a person before the end of the run-on time, the follow-up time starts again after the person has left the detection area.

*  factory-made adjustment

• Motion detector

Adjustment options:

•  Input delay continuous from 3 until 20 min


WITH MOTION DETECTOR, FOLLOW-UP AND MOTION DETECTOR CONTROL

Description:

Art.-No.: 2204 V-II 30-BM-I
Art.-No.: 2214 V-II 60-BM-I
Art.-No.: 2224 V-II 100-BM-I

Integrated after-run control for infinitely variable setting of the after-running time. Easy adjustment via potentiometer. The motion detector registers persons in the detection area and triggers a switching signal. The fan starts immediately. If the person leaves the detection area, the fan terminates its operation after 15 min * after-running time. If the motion detector detects a person before the end of the run-on time, the follow-up time starts again after the person has left the detection area. Intermittent operation starts after the last fan shutdown. The fan is out of operation for the preset interval time of approx. 1 h *. The fan then runs for 15 min *.

* factory-made adjustment

• Motion detector

Adjustment options:
• Input delay continuous from 3 until 20 min
• Interval mode continuous from 1 h until 12 h

With Humidity control

Description:

Art.-No.: 2217 V-II 60-F
Art.-No.: 2227 V-II 100-F

The humidity controller has a fixed switching point of 75% RH (relative humidity) or reacts to one Rapid rise in moisture. After switching on, the fan starts after a measured value acquisition of approx. 50 s (60 or 100 m3 / h). After switching off, the fan runs for 15 min. If no increased humidity value is measured during this period, the fan switches off. The humidity sensor has a measuring control range of 20% to 95% rh and permanently monitors the room air humidity. The humidity sensor starts the fan in the following cases: 

• quick moisture increase regardless of the current room humidity 
• the switching point of 75% RH is exceeded.

The integrated tropical function ensures that the humidity sensor is adapted to the room climate, which changes depending on the season. In addition, the tropics function includes a running time limiter, which switches off the fan after 12 hours of continuous operation. Example of a rapid rise in humidity: The room humidity is 45% RH. When the shower starts, the fan starts up due to the rapid rise in humidity, even if the 75% rFS switching point has not yet been reached. 

• Fan operation 60 respectively 100 m3/h
• Follow-up time 15 min
• Measurement control range from 20 % until 95 % rF.
• Fixed switching point of 75% rh.
• reagiert unabhängig von der aktuellen Raumluftfeuchte (rF.) auf starken Feuchteanstieg
• Run-time limit


classicLine fan inserts with intake kit For use with two power levels

Without control

 

Bezeichnung:

Art.-No.: 2230 V-II 30/60
Art.-No.: 2240 V-II 30/100
Art.-No.: 2220 V-II 100

The fan runs continuously in basic load operation (30 m3 / h) or in rated load operation (60 or 100 m3 / h).

A switch can be used to switch between basic load operation and nominal load operation. 
• During space utilization, nominal load 60 or 100 m3 / h 
• Continuous base-load 30 m3/h

 

With follow-up control

Description:

Art.-No.: 2231 V-II 30/60-NZ
Art.-No.: 2241 V-II 30/100-NZ

Integrated Follow-up control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. The fan runs continuously in the basic load mode (30 m3 / h). After switching on, the fan runs after a switch-on delay of approx. 1 min * in nominal load operation (60 or 100 m3 / h). The fan runs after 15 min * in rated load operation. The fan then switches to the basic load mode.

*  factory-made adjustment

• Continuous base-load 30 m3/h
• Nominal duty 60 and 100 m3/h
• Run-on time Nominal load 60 or 100 m3 / h

Adjustment options:
• Switch-on delay infinitely variable from 3 s to 2.5 min 
• Follow-up time infinitely variable from 3 to 20 min 

 

ontact (Kopie 5)C


With comfort control

Description:

Art.-No.: 2232 V-II 30/60-K
Art.-No.: 2242 V-II 30/100-K

Integrated after-run control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. After switching on, the fan runs after a switch-on delay of approx. 1 min * in basic load operation (30 m3 / h). After switching off, the fan runs for 15 min * in nominal load operation (60 or 100 m3 / h). The fan then switches off.

* factory-made adjustment

• During the use of the room ground load 30 m3 / h 
• Run-on time Nominal load 60 or 100 m3 / h


Adjustment options:

• Switch-on delay infinitely variable from 3 s to 2.5 min
• Follow-up time infinitely variable from 3 to 20 min 

With comfort control and remote control input (potential free 230V ~)

Description:

Art.-No.: 2233 V-II 30/60-KF
Art.-No.: 2243 V-II 30/100-KF

Integrated after-run control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. After switching on, the fan runs after a switch-on delay of approx. 1 min * in basic load operation (30 m3 / h). After switching off, the fan runs for 15 min * in nominal load operation (60 or 100 m3 / h). The fan then switches off.

* factory-made adjustment

• During space utilization, base load 30 m3 / h 
• Follow-up time nominal load 60 or 100 m3 / h
• Basic load can be switched on or off via switch provided by the customer

Adjustment options:
• Switch-on delay infinitely variable from 3 s to 2.5 min 
• Follow-up time infinitely variable from 3 to 20 min 


with comfort control and remote control input (230V ~)

Description:

Art.-No.: 2233-1 V-II 30/60-KF-LX
Art.-No.: 2243-1 V-II 30/100-KF-LX

Integrated after-run control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. After switching on, the fan runs after a switch-on delay of approx. 1 min * in basic load operation (30 m3 / h). After switching off, the fan runs for 15 min * in nominal load operation (60 or 100 m3 / h). The fan then switches off.

* factory-made adjustment

• During the use of the room ground load 30 m3 / h 
• Follow-up time nominal load 60 or 100 m3 / h
• Basic load can be switched on or off via switch provided by the customer

Adjustment options:
• Switch-on delay infinitely variable from 3 s to 2.5 min 
• Follow-up time infinitely variable from 3 to 20 min

With comfort control and central control input (12 / 24V)

Description:

Art.-No.: 2234 V-II 30/60-KZ
Art.-No.: 2244 V-II 30/100-KZ

Integrated follow-up control for infinitely variable setting of the switch-on delay and follow-up time. Easy adjustment via potentiometer. After switching on, the fan runs after a switch-on delay of approx. 1 min * in basic load operation (30 m3 / h). After switching off, the fan runs for 15 min * in nominal load operation (60 or 100 m3 / h). The fan then switches off. This control is additionally equipped with a central control input for a 12/24 V control cable provided by the customer in order to switch the basic load operation on and off from a central point. 

* factory-made adjustment

• During space utilization base load 30 m3/h
• Follow-up time nominal load 60 or 100 m3/h
• Basic load can be switched on or off via switch provided by the customer


Adjustment options:

• Switch-on delay infinitely variable from 3 s to 2.5 min 
• Follow-up time infinitely variable from 3 to 20 min 


With humidity control

Description:

Art.-No.: 2235 V-II 30/60-F
Art.-No.: 2245 V-II 30/100-F

The humidity controller has a fixed setpoint of 75% rh (relative humidity) or reacts to a rapid rise in humidity. After switching on, the fan runs after a measured value acquisition of approx. 50 s in basic load operation (30 m3 / h). After switching off, the fan runs for 15 min * in nominal load operation (60 or 100 m3 / h). If no increased humidity value is measured during this period, the fan switches off. The humidity sensor has a measuring control range of 20% to 95% rh and permanently monitors the room air humidity. The humidity sensor switches the fan into the basic load mode in the following cases:


• Rapid rise in humidity independent of the current room air humidity 
• The switching point of 75% RH is exceeded.

The integrated tropical function ensures that the humidity sensor is adapted to the room climate, which changes depending on the season. In addition, the tropical function includes a running time limiter, which switches off the basic load operation of the fan after 12 hours of continuous operation.

Example of a rapid rise in moisture: The room humidity is 45% rh. When the shower is switched on, the fan switches to the basic load mode due to the rapid rise in humidity, even if the 75% RH switching point has not yet been reached. 

* factory-made adjustment

• During space utilization base load 30 m3/h
• Follow-up time nominal load 60 or 100 m3/h
• HUmidity operation base load 30 m3/h

(2) In conjunction with Option Art. 2250-01 V-II O / F-DG Ventilation according to DIN 18017-3